High Voltage Air Core Reactor
Auther: Pubdate:2020-07-15
For the whole power grid system, including transformers and loads, its main display inductance, characteristics, and reactive power compensation devices are apparent capacitance characteristics. If the resistance characteristics of the system are ignored, LC oscillation circuit will be formed. Therefore, the LC oscillation circuit will be formed between the system and the capacitor at a specific harmonic frequency when the pure capacitor is used to compensate the system with harmonic background. The direct consequence of oscillation is the breakdown of compensation capacitor and the stability of the whole power supply system. Reactor design plays a lot of roles, and the fundamental function of series reactor in compensation circuit is to break LC oscillation circuit and eliminate resonance completely. Because the inductance of the reactor increases with the increase of frequency and the capacitance of the capacitor decreases with the increase of frequency, when the fundamental frequency is 50/60 Hz, the inductance of the series reactor is less than the capacitance of the capacitor. The capacitance of the compensation circuit can be effectively compensated for reactive power. Under the background of harmonic frequency, the inductance of the designed reactor is larger than that of the capacitor, and the apparent inductance of the compensation system can be eliminated while eliminating the resonance.
 
Reactor Classification
 
Reactors can be divided into current limiting reactor, filter reactor and smoothing reactor according to their functions. Current limiting reactor is mainly used to suppress switching inrush current, filter reactor is mainly used to filter circuit and absorb harmonics, smoothing reactor is mainly used to suppress the influence of intermediate frequency components on power grid, and also plays a filtering role. All kinds of reactors have the function of restraining switching inrush current. According to the difference of structure and cooling medium, it can be divided into: hollow core, iron core, dry type and oil-immersed type. Low-voltage filter series reactor is generally designed as dry core, while high-voltage series reactor is mostly hollow core when used in large capacity compensation. Small capacity compensation is due to cost-effective. The working principle and production process of reactor can be divided into many types, such as phase-controlled reactance, balanced reactance, in-and-out line reactance, choke reactance, saturated Self-saturated reactance and so on. WEBER Electric develops and manufactures various types of high and low voltage reactor by itself, which can meet the needs of harmonic filtering in different occasions. At the same time, it can customize the exclusive reactor according to the special needs of customers.
 
technical parameter
Rated voltage: 3KV-10KV (three-phase 3.5KV/6KV/10KV)
Grid Frequency: 50/60Hz
Matching capacitor capacity: 100 - 5000Kvar
Phase,: 3/1 Phase
Type: Dry Iron Core Hollow Core
Reactance: 6%
Conductor type: copper (aluminum needs customization)
Inductance deviation: soil 3%
Linearity: 1.8In
Insulation level: winding-core 35KV
Temperature Grade: F (155C), H (180C) can be customized
Vacuum impregnation of polyester resin
Continuous overflow capacity: 1.8In
 
Ambient temperature: - 10 ~ + 45C
 
Temperature protection: built-in 120 "C temperature protection switch
 
Cooling mode: natural cooling
 
Protection Level: IP00
 
Installation environment: indoor installation